XM3.1-915-HP
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM3.1-915-HP
Firmware V1.02.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 122.31 V
Current 5.54 A
Power 577 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 577 Wh
Output
Voltage 87.90 V
Power 461 W
Apparent Power 513.33 VA
Frequency 60.02 Hz
Percent Load 38.90 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 5.84 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Disable
Total Standby Events 89
Time Since Last Standby Event 144d 12h:22m
Time in Last Standby Event 0d 0h:01m
Total Time in Standby 697 min
Standby Events Since Reset 26
Time in Standby Since Reset 76 min
Time Since Reset 1,060 day(s)
Total Run Time 1,060 day(s)
Transformer Run Time 1,060 day(s)
Total Downtime 0d 0h:00m
Oil Cap Lifespan Consumed 28.5 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 23 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 