XM3.1-915-HP
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM3.1-915-HP
Firmware V1.02.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 120.96 V
Current 5.49 A
Power 579 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 10,092 Wh
Output
Voltage 87.83 V
Power 464 W
Apparent Power 516.44 VA
Frequency 60.05 Hz
Percent Load 39.20 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 5.88 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Disable
Total Standby Events 79
Time Since Last Standby Event 85d 7h:37m
Time in Last Standby Event 0d 0h:01m
Total Time in Standby 626 min
Standby Events Since Reset 23
Time in Standby Since Reset 75 min
Time Since Reset 845 day(s)
Total Run Time 845 day(s)
Transformer Run Time 845 day(s)
Total Downtime 0d 0h:00m
Oil Cap Lifespan Consumed 23.9 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 21 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 
Copyright © 2021 Alpha Technologies Services, Inc. - an EnerSys company